• Product Name :

    TS-24BNC5 Coaxial Surge Protection

  • Instruction

    ♦ TS-24BNC5 Coaxial Surge Protection is designed according to IEC 61643-21; GB 18802.21; YD/T 1542 for protecting coaxial cable transmission devices from interruption caused by surge current, surge protection for up to 24 pcs BNC connection, provide reliable protection for coaxial cable transmission devices or video signal transmission devices from surge, operating over voltage and electrostatic. 

    ♦ Product Size

    TS-24BNC5-Coaxial-Surge-Protection-Professional

     

    ♦ Basic Circuit Diagram

    TS-24BNC5-Coaxial-Surge-Protection-High-Quality

    ♦ Technical Data 

    Model 

     

    TS-24BNC5

    Nominal voltage 

    Un

    5V-

    Rated voltage (max. continuous voltage) 

    Uc

    8V-

    Lightning Impulse Current (10/350) 

    Iimp

    0.5KA

    Nominal discharge current (8/20) 

    In

    2.5kA(line-shield)

    5kA(shield-PG)

    Max. discharge current (8/20) 

    Imax

    5kA(line-shield)

    10kA(shield-PG)

    Voltage protection level at In 

    Up

    ≤25V(line-shield)  

    Voltage protection level at 1kV/µs 

    Up

    ≤15V(line-shield)

    ≤600V(line/shield-PG) 

    Response time 

    tA

    ≤1ns (line- shield)

    ≤100ns (shield-PG) 

    Bandwidth 

    fG

    300MHz 

    Max. data transmission rates 

    Vs

    16Mbits/s 

    Operating temperature range

     

    -40°C ~ +80°C

    Relative humidity

     

    ≤ 95% (25°C)

    Connection (input / output) 

     

    BNC(socket/plug) 

    Mounting on 

     

    19'' distribution cabinet

    Earthing via

     

    Earthing screw

    Shield earthing

     

    Indirectly via integrated spark gap

    Standards 

     

    IEC 61643-21; GB 18802.21; YD/T 1542 

    Certification 

     

    CE(LVD,EMC)

     MAIN CHARACTER 

    1, Good discharge capacity, low voltage protection level
    2, Multiple protection, quick response, no interruption
    3, For installation standard 19'' distribution cabinet.

    INSTALLATION INSTRUCTION 

    1. This Coaxial Surge Protection is connected in series to the protected device.

    2. Mount the Coaxial Surge Protection on 35 mm DIN rail.

    3. The out terminal should be connected to the protected devices.

    4. Coaxial Surge Protection's earthing terminal must be connected to nearby earthing Busbar or the metal earthing enclosure of protected device.

    Regularly inspect the operating status, especially after lightning, once the communication is off, electrician should check/replace the Coaxial Surge Protection

    INSTALLATION DIAGRAM

    TS-24BNC5-Coaxial-Surge-Protection-In-China

    WARNING:

     1, The device must be installed by electrically skilled person, conforming to national standards and safety regulations.

     2, It is recommended that installation should be done under power off condition.