• Product Name :

    TS-EX24 Hazardous Surge Protector

  • Instruction

    TS-EX24 Hazardous Surge Protector is designed in accordance with IEC-61643-21, GB18802.21, YD/T 1542 standard, installed at LPZ OB-2 or higher inside the control equipment, the built-in cable connected with the control equipment’s wiring terminal and applied in the 4-20mA measuring control system and bus system in hazardous areas

    ♦ Product Size

    TS-EX24-Hazardous-Surge-Protector-Customized


    ♦ Basic Circuit Diagram

    TS-EX24-Hazardous-Surge-Protector-Picture


    ♦ Technical Data 

    Model Number

     

    TS-EX24 

    Normal Voltage

    Un

    24V-

    Rated voltage (max. continuous voltage)

    Uc

    32V-

    22.6V ~

    Lightning impulse current (10/350)

    Iimp

    1.5kA

    Normal current

    IL

    0.55A

    Nominal discharge current (8/20)

    In

    10kA (per line); 10kA(total)

    Voltage protection level at In

    Up

    ≤ 58V (line/line); ≤ 1700V (line/PG)

    Voltage protection level at 1kV/μs

    Up

    ≤ 50V (line/line); ≤ 1200V (line/PG)

    Bandwidth

    fG

    67MHz

    Capacitance

    C

    ≤ 25pF (line/line); ≤ 15pF (line/PG)

    Operating temperature range

     

    -40 0C ~ +80 0C

    Mounting in

     

    M20 x 1.5 screws

    Connection (input / output)

     

    1.3 mm x 250mm length of the connecting lead

    Earthing via

     

    Connecting lead

    Enclosure material

     

    Stainless steel case

    Test standards

     

    IEC-61643-21, GB18802.21, YD/T 1542 

    Compliance   CE


     MAIN CHARACTER 

    1, Small & easy replacement.

    2, Easy to install inside the control equipment.

    3, Stainless steel housing, fireproof & explosion-proof outdoor use.

    Installation Instruction 

    1. Screwing into the wiring port of the control equipment directly

    2. Blue wire connecteed with signal port “+”, Black Wire connected with signal port “-”

    3. Yellow / Green wire connect with grounding port “GN” of grounding system.

    4. After installation, check if commuication is be operating normally.

    Regularly inspect the operating status, especially after lightning. Once the communication is off,  electrician should check/replace the SPD.


    INSTALLATION DIAGRAM

    TS-EX24-Hazardous-Surge-Protector-Picture

    WARNING:  

    1, he device must be installed by electrically skilled person, conforming to national standards and safety regulations.

    2, It is recommended that installation should be done under power off condition.