Hazardous-Area Surge Arrester
Home » Lightning Products » IT Surge Protection » Hazardous-Area Surge Arrester
Instruction
TS-EX24 Hazardous Surge Protector is designed in accordance with IEC-61643-21, GB18802.21, YD/T 1542 standard, installed at LPZ OB-2 or higher inside the control equipment, the built-in cable connected with the control equipment’s wiring terminal and applied in the 4-20mA measuring control system and bus system in hazardous areas
♦ Product Size
♦ Basic Circuit Diagram
♦ Technical Data
Model Number |
|
TS-EX24 |
Normal Voltage |
Un |
24V- |
Rated voltage (max. continuous voltage) |
Uc |
32V- 22.6V ~ |
Lightning impulse current (10/350) |
Iimp |
1.5kA |
Normal current |
IL |
0.55A |
Nominal discharge current (8/20) |
In |
10kA (per line); 10kA(total) |
Voltage protection level at In |
Up |
≤ 58V (line/line); ≤ 1700V (line/PG) |
Voltage protection level at 1kV/μs |
Up |
≤ 50V (line/line); ≤ 1200V (line/PG) |
Bandwidth |
fG |
67MHz |
Capacitance |
C |
≤ 25pF (line/line); ≤ 15pF (line/PG) |
Operating temperature range |
|
-40 0C ~ +80 0C |
Mounting in |
|
M20 x 1.5 screws |
Connection (input / output) |
|
1.3 mm x 250mm length of the connecting lead |
Earthing via |
|
Connecting lead |
Enclosure material |
|
Stainless steel case |
Test standards |
|
IEC-61643-21, GB18802.21, YD/T 1542 |
Compliance | CE |
♦ MAIN CHARACTER
1, Small & easy replacement.
2, Easy to install inside the control equipment.
3, Stainless steel housing, fireproof & explosion-proof outdoor use.
Installation Instruction 1. Screwing into the wiring port of the control equipment directly 2. Blue wire connecteed with signal port “+”, Black Wire connected with signal port “-” 3. Yellow / Green wire connect with grounding port “GN” of grounding system. 4. After installation, check if commuication is be operating normally. Regularly inspect the operating status, especially after lightning. Once the communication is off, electrician should check/replace the SPD. |
INSTALLATION DIAGRAM |
WARNING: 1, he device must be installed by electrically skilled person, conforming to national standards and safety regulations. 2, It is recommended that installation should be done under power off condition. |
- CONTACT US
- 0086 13926098193
- 0086 20 28819702 EXT 27806
- [email protected]
- Hongdiyuan Industrial Park, Wufeng Avenue, Linjiang Town, Jiangdong New District, Heyuan, Guangdong,P.R.C.
- http://www.tslpro.com
- +86 13926098193
- F13926098193
- tslpro.tstlp